Outback-power-systems MATE2 System Controller and Display Installation a Manuale Utente Pagina 76

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
Vedere la pagina 75
76
eAGSSetupmenucontainsthefollowinggeneralsettingsthatdenetheAGSroutines.
eMATEusestheAUXoutputofanFXorFLEXnetDCrelaytocontrolthegenerator.e
MATEisconnectedtothisFXeitherdirectlyorthroughaHUB.
IfaHUBisused:
• Usethe<INC> and <DEC>sokeystosettheAGSPortvaluetotheHUBFXorFLEXnet
DC Port controlling the generator.
IfnoHUBisusedandtheMATEisdirectlypluggedintoanFX,thentheAGSPortneedstobe
setto0(zero).
ADV/MATE/AGS/SETUP-------------
ags port: 0
DOWN AGS INC DEC
ADV/MATE/AGS/SETUP---------------
ags port: 3
DOWN AGS INC DEC
Example:
AMATEisconnectedtoaHUB-10thathasfour
FXsandthreeChargeControllersconnectedtoit.
eFXsarepluggedintoPorts1–4,aslabeledon
theHUB,andtheChargeControllersareplugged
intoPorts5–7.AnyFXcanhaveitsAUXoutput
wired to a relay whose contacts are wired to the
startingcircuitryofthegenerator.eAGSPort
mustbesettotheportofthechosenFX.
AersettingtheAGSPort,pressthe<DOWN>
sokey.enextscreenallowsyoutoenablethe
AGSMode.
AGS Port
Vedere la pagina 75